Range of Application
Items Specification
Operating Ambient Temperature -25°C~+45°C (average not exceeding 35°C within 24 hours)
Maximum Permissible Overcurrent Within 130% of rated current
Maximum Permissible Capacity (VA) Within 135% of rated capacity (VA)
Capacity Tolerance Within -5% to +15% of rated capacity (imbalance rate: within 108%)
Loss Rate Within 0.15% (at 20°C and 70°C, rated voltage)
Withstand voltage test · Between terminals: Rated voltage x 1.75 for 1 minute
Between terminals and external case: 3000VAC for 1 minute
Insulation Resistance Between terminals and external case: 2,000MΩ or more
Sealing No oil leakage
Built-in Voltage Discharge Residual voltage after opening from the power source should be below 75V within 3 minutes
Built-in Safety Device Equipped with pressure-sensitive cut-off type safety device
Impregnant Capacitor-specific oil (non-PCB)
Compliance Standards KS C4801, JIS C4901, IEC Pub.70A
Maximum Allowable Overvoltage
Overvoltage Percentage (%) Duration of Overvoltage Application
110 Within 8 hours out of 24 hours
115 Within 30 hours out of 24 hours
120 2 times within 1 month for a duration of within 5 minutes each time
130 2 times within 1 month for a duration of within 1 minute each time
Drawing of Product

· DLE-Series (N1-Type)

image
DLE-Series
(E-Type)
image
Range of Application
Items Specification
Operating Ambient Temperature -25°C~+45°C (average not exceeding 35°C within 24 hours)
Maximum Permissible Overcurrent Within 130% of rated current
Maximum Permissible Capacity (VA) Within 135% of rated capacity (VA)
Capacity Tolerance Within -5% to +15% of rated capacity (imbalance rate: within 108%)
Loss Rate Within 0.15% (at 20°C and 70°C, rated voltage)
Withstand voltage test · Between terminals : Rated voltage x 1.75 for 1 minute
· Between terminals and external case : 1,800VAC for 1 minute at rated voltage of 220VAC / 3,000VAC for 1 minute at rated voltage of 380-480VAC.d
Insulation Resistance Between terminals and external case : 1,000MΩ or more at 220VAC / 3,000MΩ or more at 380-480VAC
Sealing No oil leakage
Built-in Voltage Discharge Residual voltage after opening from the power source should be below 75V within 3 minutes
Built-in Safety Device Equipped with pressure-sensitive cut-off type safety device
Impregnant Capacitor-specific oil (non-PCB)
Painting Color Munsell 8.8GY 7.4/3.4 Epoxy Paint
Compliance Standards KS C4801, JIS C4901, IEC Pub.70A
Maximum Allowable Overvoltage
Overvoltage Percentage (%) Duration of Overvoltage Application
110 Within 8 hours out of 24 hours
115 Within 30 hours out of 24 hours
120 2 times within 1 month for a duration of within 5 minutes each time
130 2 times within 1 month for a duration of within 1 minute each time